DELTA DVP04PT-S PLC analog kirish-chiqish moduli
Texnik xususiyatlari
- Model: DVP04/06PT-S
- Kirish: RTD ning 4/6 nuqtasi
- Chiqish: 16-bitli raqamli signallar
- O'rnatish: boshqaruv shkafi chang, namlik, elektr toki urishi va tebranishsiz
- Olchamlari: 90.00 mm x 60.00 mm x 25.20 mm
- Ochiq turdagi qurilma
- Alohida quvvat bloki
Mahsulotdan foydalanish bo'yicha ko'rsatmalar
O'rnatish bo'yicha ko'rsatmalar
- Boshqaruv shkafi havodagi chang, namlik, elektr toki urishi va tebranishlardan tozalanganligiga ishonch hosil qiling.
- Ruxsatsiz kirish yoki baxtsiz hodisalarning oldini olish uchun himoya vositalaridan foydalaning.
- AC quvvatini har qanday kiritish/chiqarish terminallariga ulashdan saqlaning.
Quvvatlanmoqda
- Qurilmani yoqishdan oldin barcha simlarni ikki marta tekshiring.
- Qurilmani uzganingizdan so'ng bir daqiqa davomida har qanday terminalga tegmang.
- Elektromagnit shovqinlarni oldini olish uchun terminalni to'g'ri erga ulang.
Tashqi simlar
- To'g'ri ulanish uchun qo'llanmada ko'rsatilgan ulanish sxemasiga amal qiling.
- Signalning yaxlitligini yaxshilash uchun ekranlangan kabellardan foydalaning.
- Shovqin shovqinini kamaytirish uchun simlarni iloji boricha qisqa tuting.
Kirish
Delta DVP seriyali PLC ni tanlaganingiz uchun tashakkur. DVP04/06PT-S RTD ning 4/6 nuqtasini qabul qilish va ularni 16 bitli raqamli signallarga aylantirish imkoniyatiga ega. DVP Slim seriyali MPU dasturidagi FROM/TO ko'rsatmalari orqali ma'lumotlarni o'qish va yozish mumkin. Modullarda ko'plab 16-bitli boshqaruv registrlari (CR) mavjud. Quvvat bloki undan alohida va kichik o'lchamli va o'rnatish oson.
DVP04/06PT-S Ochiq toifadagi qurilma. U havodagi chang, namlik, elektr toki urishi va tebranishlarsiz boshqaruv kabinasiga o'rnatilishi kerak. Texnik xizmat ko'rsatmaydigan xodimlarning DVP04/06PT-S dan foydalanishiga yo'l qo'ymaslik yoki avariya DVP04/06PT-S ga zarar yetkazmaslik uchun DVP04/06PT-S o'rnatilgan boshqaruv kabinasi himoya vositasi bilan jihozlangan bo'lishi kerak. Misol uchunample, DVP04/06PT-S o'rnatilgan boshqaruv shkafi maxsus asbob yoki kalit bilan qulfdan chiqarilishi mumkin.
AC quvvatini kiritish/chiqarish terminallarining birortasiga ulamang, aks holda jiddiy shikastlanishlar yuzaga kelishi mumkin. DVP04/06PT-S ni yoqishdan oldin barcha simlarni qayta tekshiring. DVP04/06PT-S uzilgandan so'ng, bir daqiqa ichida hech qanday terminalga tegmang. Tuproq terminali ekanligiga ishonch hosil qiling DVP04/06PT-S da elektromagnit shovqinlarni oldini olish uchun to'g'ri erga ulangan.
Mahsulot Profile & Hajmi
1. Holat indikatori (POWER, RUN va ERROR) | 2. Model nomi | 3. DIN relsli klip |
4. I/U terminallari | 5. Kirish/chiqish nuqtasi indikatori | 6. O'rnatish teshiklari |
7. Spetsifikatsiya yorlig'i | 8. I/U modulining ulanish porti | 9. I/U moduli klipi |
10. DIN ray (35 mm) | 11. I/U moduli klipi | 12. RS-485 aloqa porti (DVP04PT-S) |
13. Quvvat ulash porti (DVP04PT-S) |
14. I/U ulanish porti |
Simlarni ulash
I/U terminali tartibi
Tashqi simlar
Eslatmalar
- Analog kiritish uchun faqat harorat sensori bilan o'ralgan va boshqa quvvat liniyasidan yoki shovqinga olib kelishi mumkin bo'lgan simlardan ajratilgan simlardan foydalaning.
- 3-simli RTD sensori tel qarshiligini olib tashlash uchun ishlatilishi mumkin bo'lgan kompensatsiya halqasini ta'minlaydi, 2-simli RTD sensori esa kompensatsiya qilish mexanizmiga ega emas. Bir xil uzunlikdagi (3 m dan kam) va sim qarshiligi 200 ohmdan kam bo'lgan kabellardan (20 simli) foydalaning.
- Shovqin bo'lsa, ekranlangan kabellarni tizimning yerga ulash nuqtasiga ulang, so'ngra tizimning tuproqli nuqtasini erga ulang yoki uni tarqatish qutisiga ulang.
- Iltimos, modulni harorati o'lchanadigan qurilmaga ulashda simlarni iloji boricha qisqa tuting va shovqin shovqinini oldini olish uchun ishlatiladigan quvvat kabelini yukga ulangan kabeldan iloji boricha uzoqroq tuting.
- Iltimos, ulaning
quvvat manbai modulida va
harorat modulida tizimni erga ulang, so'ngra tizimni erga ulang yoki tizimni tarqatish qutisiga ulang.
Texnik xususiyatlari
Elektr texnik xususiyatlari
Maks. nominal quvvat sarfi | 2W |
Operatsion/saqlash | Ishlash: 0 ° C ~ 55 ° C (harorat), 5 ~ 95% (namlik), ifloslanish darajasi 2
Saqlash: -25°C~70°C (harorat), 5~95% (namlik) |
Vibratsiyaga / zarbaga qarshilik | Xalqaro standartlar: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 va IEC 68-2-27 (TEST Ea) |
DVP-PLC MPU ga ketma-ket ulanish |
Modullar MPU dan masofasiga qarab avtomatik ravishda 0 dan 7 gacha raqamlanadi. No.0 MPUga eng yaqin, №7 esa eng uzoqdir. Maksimal
8 ta modul MPU ga ulanishi mumkin va hech qanday raqamli I/U nuqtalarini egallamaydi. |
Funktsional xususiyatlar
DVP04/06PT-S | Selsiy (°C) | Farengeyt (°F) |
Analog kirish kanali | Har bir modul uchun 4/6 kanal | |
Sensorlar turi | 2-simli/3-simli Pt100 / Pt1000 3850 PPM/°C (DIN 43760 JIS C1604-1989)
/ Ni100 / Ni1000 / LG-Ni1000 / Cu100 / Cu50/ 0~300ũ/ 0~3000ũ |
|
Hozirgi qo'zg'alish | 1.53mA / 204.8uA | |
Haroratni kiritish diapazoni | Iltimos, harorat/raqamli qiymat xarakteristikasi egri chizig'iga qarang. | |
Raqamli konvertatsiya diapazoni | Iltimos, harorat/raqamli qiymat xarakteristikasi egri chizig'iga qarang. | |
Rezolyutsiya | 0.1 ° S | 0.18° F |
Umumiy aniqlik | 0.6 ~ 0°C (55 ~ 32°F) davomida toʻliq shkalaning ±131% | |
Javob vaqti | DVP04PT-S: 200ms/kanal; DVP06PT-S: 160/ms/kanal | |
Izolyatsiya usuli
(raqamli va analog sxemalar o'rtasida) |
Kanallar o'rtasida hech qanday izolyatsiya yo'q.
Raqamli/analog zanjirlar o'rtasida 500VDC va tuproqli 500VDC analog va raqamli davrlar o'rtasida 500VDC 24VDC va yer o'rtasida |
|
Raqamli ma'lumotlar formati | 2 ning 16 bitli to'ldiruvchisi | |
O'rtacha funktsiya | Ha (DVP04PT-S: CR#2 ~ CR#5 / DVP06PT-S: CR#2) | |
O'z-o'zini diagnostika funktsiyasi | Har bir kanalda yuqori/pastki chegarani aniqlash funksiyasi mavjud. | |
RS-485 aloqa rejimi |
Qo'llab-quvvatlanadi, shu jumladan ASCII/RTU rejimi. Standart aloqa formati: 9600, 7, E, 1, ASCII; aloqa formati haqida batafsil ma'lumot uchun CR#32 ga qarang.
Eslatma1: RS-485 protsessor seriyali PLClarga ulanganda ishlatilmaydi. Eslatma 2: RS-485 aloqa sozlamalari haqida batafsil ma'lumot olish uchun DVP dasturlash qo'llanmasining E ilovasidagi Slim Type Maxsus modul aloqalariga qarang. |
* 1: Harorat birligi 0.1°C/0.1°F sifatida ko'rsatiladi. Agar harorat birligi Farengeyt qilib o'rnatilsa, ikkinchi kasr ko'rsatilmaydi.
Nazorat registri
CR# | Manzil | Qulflangan | Atribut | Kontentni ro'yxatdan o'tkazish | Tavsif | |||
#0 | H'4064 | O | R | Model nomi
(Tizim tomonidan sozlangan) |
DVP04PT-S model kodi = H'8A
DVP06PT-S model kodi = H'CA |
|||
#1 |
H'4065 |
X |
R/W |
CH1~CH4 rejimini sozlash |
b15~12 | b11~8 | b7~4 | b3~0 |
CH4 | CH3 | CH2 | CH1 | |||||
Masalan, CH1 rejimini (b3,b2,b1,b0) olingample.
1. (0,0,0,0): Pt100 (standart) 2. (0,0,0,1): Ni100 3. (0,0,1,0): Pt1000 4. (0,0,1,1): Ni1000 5. (0,1,0,0): LG-Ni1000 6. (0,1,0,1): Cu100 7. (0,1,1,0): Cu50 8. (0,1,1,1): 0~300 Ō 9. (1,0,0,0): 0~3000 Ō 10. (1,1,1,1)Kanal o'chirilgan. 8 va 9 rejimlari faqat DVP04PT-S V4.16 yoki undan keyingi versiyalari uchun mavjud va DVP06PT-S V4.12 yoki undan keyingi versiyalari. |
||||||||
#2 |
H'4066 |
O |
R/W |
DVP04PT-S: CH1 o'rtacha soni |
CH1 da "o'rtacha" haroratni hisoblash uchun ishlatiladigan o'qishlar soni.
Sozlash diapazoni: K1~K20. Standart sozlama K10. |
|||
— |
DVP06PT-S: CH1~CH6 o'rtacha soni |
CH1 ~ 6 bo'yicha "o'rtacha" haroratni hisoblash uchun ishlatiladigan ko'rsatkichlar soni.
Sozlash diapazoni: K1~K20. Standart sozlama K10. |
||||||
#3 |
H'4067 |
O |
H'4067 |
DVP04PT-S: CH2 o'rtacha soni |
CH2 da "o'rtacha" haroratni hisoblash uchun ishlatiladigan o'qishlar soni.
Sozlash diapazoni: K1~K20. Standart sozlama K10. |
|||
#4 |
H'4068 |
O |
H'4068 |
DVP04PT-S: CH3 o'rtacha soni |
CH3 da "o'rtacha" haroratni hisoblash uchun ishlatiladigan o'qishlar soni.
Sozlash diapazoni: K1~K20. Standart sozlama K10. |
|||
#5 |
H'4069 |
O |
H'4069 |
DVP04PT-S: CH4 o'rtacha soni |
CH4 da "o'rtacha" haroratni hisoblash uchun ishlatiladigan o'qishlar soni.
Sozlash diapazoni: K1~K20. |
#6 | H'406A | X | R | CH1 o'rtacha darajalari | DVP04PT-S:
CH1 ~ 4 DVP06PT-S uchun o'rtacha darajalar: CH1 ~ 6 uchun o'rtacha darajalar Birlik: 0.1°C, 0.01 Ō (0~300 Ō), 0.1 Ō (0~3000 Ō) |
||||
#7 | H'406B | X | R | CH2 o'rtacha darajalari | |||||
#8 | H'406C | X | R | CH3 o'rtacha darajalari | |||||
#9 | H'406D | X | R | CH4 o'rtacha darajalari | |||||
#10 | — | X | R | CH5 o'rtacha darajalari | |||||
#11 | — | X | R | CH6 o'rtacha darajalari | |||||
#12 | H'4070 | X | R | CH1 o'rtacha darajalari | DVP04PT-S:
CH1 ~ 4 DVP06PT-S uchun o'rtacha darajalar: CH1 ~ 6 birligi uchun o'rtacha darajalar: 0.1°F, 0.01 Ō (0~300 Ō), 0.1 Ō (0~3000 Ō) |
||||
#13 | H'4071 | X | R | CH2 o'rtacha darajalari | |||||
#14 | H'4072 | X | R | CH3 o'rtacha darajalari | |||||
#15 | H'4073 | X | R | CH4 o'rtacha darajalari | |||||
#16 | — | X | R | CH5 o'rtacha darajalari | |||||
#17 | — | X | R | CH6 o'rtacha darajalari | |||||
#18 | H'4076 | X | R | Hozirgi harorat. CH1 | DVP04PT-S:
CH 1~4 DVP06PT-S ning hozirgi harorati: CH1~6 ning hozirgi harorati: 0.1°C, 0.01 Ō (0~300 Ō), 0.1 Ō (0~3000 Ō) |
||||
#19 | H'4077 | X | R | Hozirgi harorat. CH2 | |||||
#20 | H'4078 | X | R | Hozirgi harorat. CH3 | |||||
#21 | H'4079 | X | R | Hozirgi harorat. CH4 | |||||
#22 | — | X | R | Hozirgi harorat. CH5 | |||||
#23 | — | X | R | Hozirgi harorat. CH6 | |||||
#24 | H'407C | X | R | Hozirgi harorat. CH1 |
DVP04PT-S: Hozirgi harorat CH 1~4 DVP06PT-S: CH 1~6 ning hozirgi harorati: 0.1°F, 0.01 Ō (0~300 Ō), 0.1 Ō (0~3000 Ō) |
||||
#25 | H'407D | X | R | Hozirgi harorat. CH2 | |||||
#26 | H'407E | X | R | Hozirgi harorat. CH3 | |||||
#27 | H'407F | X | R | Hozirgi harorat. CH4 | |||||
#28 | — | X | R | Hozirgi harorat. CH5 | |||||
#29 | — | X | R | Hozirgi harorat. CH6 | |||||
#29 |
H'4081 |
X |
R/W |
DVP04PT-S: PID rejimini sozlash |
H'5678ni PID rejimi sifatida va boshqa qiymatlarni oddiy rejim sifatida o'rnating
Standart qiymat H'0000. |
||||
#30 |
H'4082 |
X |
R |
Xato holati |
Ma'lumotlar registri xato holatini saqlaydi. Tafsilotlar uchun xato kodlari jadvaliga qarang. | ||||
#31 |
H'4083 |
O |
R/W |
DVP04PT-S:
Aloqa manzilini sozlash |
RS-485 aloqa manzilini o'rnating; sozlash diapazoni: 01~254.
Standart: K1 |
||||
— |
X |
R/W |
DVP06PT-S:
CH5~CH6 rejimini sozlash |
CH5 rejimi: b0 ~ b3 CH6 rejimi: b4 ~ b7
Malumot uchun CR#1 ga qarang |
|||||
32 |
H'4084 |
O |
R/W |
DVP04PT-S: Aloqa formatini sozlash |
Bod tezligi uchun sozlamalar 4,800/9,600/19,200/38,400/57,600/ 115,200 bit/s.
Aloqa formati: ASCII: 7,E,1/7,O,1/8,E,1/8,O,1 / 8, N, 1 RTU: 8,E,1/8,O,1/8,N,1 Standart zavod: ASCII,9600,7,E,1 (CR#32=H'0002) Qo'shimcha ma'lumot olish uchun ushbu jadval oxiridagi ※CR#32 aloqa formati sozlamalariga qarang. |
||||
— |
X |
R/W |
DVP06PT-S: CH5~CH6 LED indikatorini sozlash xatosi |
b15~12 | b11~9 | b8~6 | b5~3 | b2~0 | |
ERR
LED |
zaxiralangan | CH6 | CH5 | ||||||
b12~13 CH5~6 ga to'g'ri keladi, bit ON bo'lsa, shkala diapazondan oshib ketadi va Xato LED indikatori yonadi. | |||||||||
#33 |
H'4085 |
O |
R/W |
DVP04PT-S: CH1~CH4
Standart sozlamalarni tiklash va xato LED ko'rsatkich sozlamalari |
|||||
b15~12 | b11~9 | b8~6 | b5~3 | b2~0 | |||||
ERR
LED |
CH4 | CH3 | CH2 | CH1 | |||||
Agar b2~b0 100 ga o'rnatilgan bo'lsa, CH1 ning barcha sozlash qiymatlari qayta o'rnatiladi |
— |
X |
R/W |
DVP06PT-S: CH1~CH4 Standart sozlamalarni tiklash va CH1~CH4 Xato LED indikatori sozlamalari |
standart sozlamalarga. Barcha kanallarni asl holatiga qaytarish uchun b11~0 ni H'924 ga o'rnating (DVP04PT-S bitta va barcha kanallarni qayta o'rnatishni qo'llab-quvvatlaydi; DVP06PT-S faqat barcha kanallarni qayta tiklashni qo'llab-quvvatlaydi). b12~15 CH1~4 ga to'g'ri keladi, bit ON bo'lsa, shkala oshib ketadi
diapazon va Xato LED indikatori yonadi. |
|
#34 | H'4086 | O | R | Dasturiy ta'minot versiyasi | Versiyani o'n oltilik tizimda ko'rsatish. masalan:
H'010A = 1.0A versiyasi |
#35 ~ #48 Tizimdan foydalanish uchun | |||||
Belgilar: O qulflangan degan ma'noni anglatadi. (RS485 bilan qo'llab-quvvatlanadi, lekin MPU-larga ulanishda qo'llab-quvvatlanmaydi.)
X qulflanmagan degan ma'noni anglatadi. R degani FROM ko'rsatmasi yoki RS-485 yordamida ma'lumotlarni o'qiy oladi. W degani TO ko'rsatmasi yoki RS-485 yordamida ma'lumotlarni yozishi mumkin. |
- RESET funksiyasi faqat V04 yoki undan keyingi proshivkali 4.16PT-S modullari uchun qo‘shilgan va 06PT-S uchun mavjud emas. Modul quvvat manbaini 24 VDC ga ulang va H'4352 ni CR#0 ga yozing va keyin quvvatni o'chiring va qayta yoqing; modullardagi barcha parametrlar, shu jumladan aloqa parametrlari zavod sozlamalariga tiklanadi.
- Agar siz Modbus manzilini o'nlik formatda ishlatmoqchi bo'lsangiz, o'n oltilik registrni o'nlik formatga o'tkazishingiz va keyin uni o'nlik Modbus registr manziliga aylantirish uchun bitta qo'shishingiz mumkin. Misol uchunampCR#4064 ning “H'0” manzilini o'n oltilik formatga o'tkazsangiz, natija 16484 bo'lishi uchun va unga bitta qo'shsangiz, sizda 16485, o'nlik formatdagi Modbus manzili bo'ladi.
- CR#32 aloqa formati sozlamalari: proshivka V04 yoki oldingi versiyalari bo'lgan DVP4.14PT-S modullari uchun b11~b8 ma'lumotlar formatini tanlash mavjud emas. ASCII rejimi uchun format 7, E, 1 (H'00XX) va RTU rejimi uchun format 8, E, 1 (H'C0xx/H'80xx) ga o'rnatiladi. V4.15 yoki undan keyingi proshivkali modullar uchun sozlash uchun quyidagi jadvalga qarang. E'tibor bering, asl H'C0XX/H'80XX kodi V8 yoki undan keyingi proshivkali modullar uchun RTU, 1, E, 4.15 sifatida ko'rinadi.
b15 ~ b12 | b11 ~ b8 | b7 ~ b0 | |||
ASCII/RTU, past va yuqori bayt CRC tekshirish kodini almashtiring |
Ma'lumotlar formati |
Bod tezligi |
|||
Tavsif | |||||
H'0 | ASCII | H'0 | 7,E,1*1 | H'01 | 4800 bps |
H'8 |
RTU,
past va yuqori bayt CRC tekshirish kodini almashtirmang |
H'1 | 8,E,1 | H'02 | 9600 bps |
H'2 | zaxiralangan | H'04 | 19200 bps | ||
H'C |
RTU,
past va yuqori bayt CRC tekshirish kodini almashtiring |
H'3 | 8, N, 1 | H'08 | 38400 bps |
H'4 | 7,O,1*1 | H'10 | 57600 bps | ||
H'5 | 8.O,1 | H'20 | 115200 bps |
Eslatma * 1: Bu faqat ASCII formatida mavjud.
Masalan: RTU natijasi uchun H'C310 ni CR#32 ga yozing, past va yuqori bayt CRC tekshirish kodini, 8,N,1 va uzatish tezligini 57600 bit/s da almashtiring.
- RS-485 funktsiya kodlari: 03'H registrlardan ma'lumotlarni o'qish uchun mo'ljallangan. 06'H - registrlarga ma'lumotlar so'zini yozish uchun. 10'H registrlarga bir nechta ma'lumotlar so'zlarini yozish uchun mo'ljallangan.
- CR#30 xato kodi registridir.
- Eslatma: Har bir xato kodi tegishli bitga ega bo'ladi va 16 bitli ikkilik raqamlarga (Bit0 ~ 15) aylantirilishi kerak. Bir vaqtning o'zida ikki yoki undan ortiq xatolik yuz berishi mumkin. Quyidagi jadvalga qarang:
Bit raqami | 0 | 1 | 2 | 3 |
Tavsif |
Quvvat manbai anormal | Kontakt hech narsaga ulanmagan. |
Zaxiralangan |
Zaxiralangan |
Bit raqami | 4 | 5 | 6 | 7 |
Tavsif | Zaxiralangan | Zaxiralangan | o'rtacha raqam xatosi | Ko'rsatma xatosi |
Bit raqami | 8 | 9 | 10 | 11 |
Tavsif | CH1 Anormal konvertatsiya | CH2 Anormal konvertatsiya | CH3 Anormal konvertatsiya | CH4 Anormal konvertatsiya |
Bit raqami | 12 | 13 | 14 | 15 |
Tavsif | CH5 Anormal konvertatsiya | CH6 Anormal konvertatsiya | Zaxiralangan | Zaxiralangan |
- Harorat/raqamli qiymat xarakteristikasi egri chizig'i
Tselsiy (Farengeyt) bo'yicha haroratni o'lchash rejimi:
Sensor | Harorat diapazoni | Raqamli qiymat konvertatsiya diapazoni | ||
°C (Min./Maks.) | °F (min./maks.) | °C (Min./Maks.) | °F (min./maks.) | |
Pt100 | -180 ~ 800°C | -292 ~ 1,472 ° F | K-1,800 ~ K8,000 | K-2,920 ~ K14,720 |
Ni100 | -80 ~ 170°C | -112 ~ 338 ° F | K-800 ~ K1,700 | K-1,120 ~ K3,380 |
Pt1000 | -180 ~ 800°C | -292 ~ 1,472 ° F | K-1,800 ~ K8,000 | K-2,920 ~ K14,720 |
Ni1000 | -80 ~ 170°C | -112 ~ 338 ° F | K-800 ~ K1,700 | K-1,120 ~ K3,380 |
LG-Ni1000 | -60 ~ 200°C | -76 ~ 392 ° F | K-600 ~ K2,000 | K-760 ~ K3,920 |
Cu100 | -50 ~ 150°C | -58 ~ 302 ° F | K-500 ~ K1,500 | K-580 ~ K3,020 |
Cu50 | -50 ~ 150°C | -58 ~ 302 ° F | K-500 ~ K1,500 | K-580 ~ K3,020 |
Sensor | Kirish qarshiligi diapazoni | Raqamli qiymat konvertatsiya diapazoni | ||
0 ~ 300 Ō | 0Ō ~ 320Ō | K0 ~ 32000 | 0 ~ 300 Ō | 0Ō ~ 320Ō |
0 ~ 3000 Ō | 0Ō ~ 3200Ō | K0 ~ 32000 | 0 ~ 3000 Ō | 0Ō ~ 3200Ō |
- CR#29 H'5678 ga o'rnatilganda, CR#0 ~ CR#34 DVP04PT-S V3.08 va undan yuqori versiyalari bilan PID sozlamalari uchun ishlatilishi mumkin.
TSS
- Q: AC quvvatini I/U terminallaridan biriga ulashim mumkinmi?
- A: Yo'q, AC quvvatini har qanday kiritish/chiqarish terminallariga ulash jiddiy zararga olib kelishi mumkin. Quvvatni yoqishdan oldin har doim simlarni ikki marta tekshiring.
- Q: O'chirilgandan keyin qurilmani qanday ishlatishim kerak?
- A: Qurilmani ajratib bo'lgandan so'ng, xavfsizlikni ta'minlash uchun kamida bir daqiqa hech qanday terminalga tegmang.
- Q: Elektromagnit shovqinlarni oldini olish uchun nima qilishim kerak?
- A: Elektromagnit parazitlarni oldini olish uchun qurilmadagi tuproq terminali to'g'ri erga ulanganligiga ishonch hosil qiling.
Hujjatlar / manbalar
![]() |
DELTA DVP04PT-S PLC analog kirish-chiqish moduli [pdf] Ko'rsatmalar DVP04PT-S, DVP06PT, DVP04PT-S PLC analog kirish-chiqish moduli, DVP04PT-S, PLC analog kirish-chiqish moduli, analog kirish-chiqish moduli, kirish-chiqish moduli, chiqish moduli, modul |